This article discusses the best practice to follow while calculating the PF value and when converting the values to KVA or other units.
If your installed PEM unit is with the following model,
PDM Rev 03 740-013110 QCS1829509Z Power Distribution Module
PEM 0 Rev 11 740-027760 QCS1828N0MJ PS 4.1kW; 200-240V AC in
PEM 1 Rev 11 740-027760 QCS1828N02B PS 4.1kW; 200-240V AC in
PEM 2 Rev 01 740-063047 QCS2449N02Z PS 4.1kW; 200-240V AC in
PEM 3 Rev 11 740-027760 QCS1828N0DK PS 4.1kW; 200-240V AC in
System:
Zone 0:
Capacity: 4100 W (maximum 4100 W)
Allocated power: 2226 W (1874 W remaining)
Actual usage: 1653 W
Zone 1:
Allocated power: 1772 W (2328 W remaining)
Actual usage: 1425 W
Total system capacity: 8200 W (maximum 8200 W)
Total remaining power: 4202 W
The PF Value that will be considered is 0.97. Below are the calculations.