Description

This KB addresses the issue where the below alarm logs are observed related to PSU on QFX10k switch :

 

root@QFX> show chassis alarms

3 alarms currently active

Alarm time Class Description

2024-08-01 05:28:44 IST Major Power Budget: Insufficient Power

2024-08-01 05:25:44 IST Minor PEM 3 Output Overload

2024-08-01 05:25:44 IST Minor PEM 3 Not Powered

Symptoms

The alarm logs are observed for one of the PEM on QFX10k switch.

Solution

  • The power supply on which the issue was seen was seen in check state when looked into environment output.

 

  

   Power Supply 0         OK     31 degrees C / 87 degrees F

   Power Supply 1         OK     36 degrees C / 96 degrees F

   Power Supply 2         OK     38 degrees C / 100 degrees F

   Power Supply 3         Check

   Power Supply 4         OK     36 degrees C / 96 degrees F

   Power Supply 5         OK     38 degrees C / 100 degrees F

 

  • Below error logs is observed for the concerned PEM in chassisd logs :
Aug 1 10:25:48.145 QFX chassisd[22685]: CHASSISD_SNMP_TRAP6: SNMP trap generated: Power Supply failed (jnxContentsContainerIndex 2, jnxContentsL1Index 4, jnxContentsL2Index 0, jnxContentsL3Index 0, jnxContentsDescr Power Supply 3, jnxOperatingState 6)

 

 

 

Solution :

  • Please try to reseat the concerned PEM and check if that helps to recover the issue state.
  • If the alarm log persists or reappears after a few days, we should proceed with processing the RMA for the affected PEM as a hardware fault.