This article explains Major alarm seen on MX devices with respect to fan tray rotor failure and method to mitigate the alarm.
The below alarms will be raised on the device:
root@device> show chassis alarms no-forwarding 3 alarms currently active Alarm time Class Description 2023-02-08 02:57:43 UTC Major Fan Tray 2 Pair 0 Outer Fan stopped due to rotor failure 2023-02-08 03:18:48 UTC Major Fan Tray 2 Pair 1 Inner Fan stopped due to rotor failure 2023-02-08 03:18:48 UTC Major Fan Tray 2 Pair 0 Inner Fan stopped due to rotor failure root@device> show chassis environment no-forwarding Class Item Status Measurement Fan Tray 2 Fan 0 Failed Fan Tray 2 Fan 1 Failed Fan Tray 2 Fan 2 Failed Logs: Feb 8 02:57:43 device-re0 alarmd[9011]: Alarm set: FAN id=402653328, color=RED, class=CHASSIS, reason=Fan Tray 2 Pair 0 Outer Fan stopped due to rotor failure ----------> Major alarm set Feb 8 02:57:48 device-re0 chassisd[8595]: CHASSISD_SNMP_TRAP6: SNMP trap generated: Fan/Blower Failed (jnxContentsContainerIndex 4, jnxContentsL1Index 1, jnxContentsL2Index 1, jnxContentsL3Index 0, jnxContentsDescr Fan Tray 2 Fan 0, jnxOperatingState 2) Feb 8 02:57:48 device-re0 chassisd[8595]: CHASSISD_SNMP_TRAP6: SNMP trap generated: Fan/Blower Failed (jnxContentsContainerIndex 4, jnxContentsL1Index 1, jnxContentsL2Index 2, jnxContentsL3Index 0, jnxContentsDescr Fan Tray 2 Fan 1, jnxOperatingState 2) Feb 8 02:57:48 device-re0 chassisd[8595]: CHASSISD_SNMP_TRAP6: SNMP trap generated: Fan/Blower Failed (jnxContentsContainerIndex 4, jnxContentsL1Index 1, jnxContentsL2Index 3, jnxContentsL3Index 0, jnxContentsDescr Fan Tray 2 Fan 2, jnxOperatingState 2) Feb 8 03:18:48 device-re0 alarmd[9011]: Alarm set: FAN id=402653328, color=RED, class=CHASSIS, reason=Fan Tray 2 Pair 0 Inner Fan stopped due to rotor failure ----------> Major alarm set Feb 8 03:18:48 device-re0 alarmd[9011]: Alarm set: FAN id=402653328, color=RED, class=CHASSIS, reason=Fan Tray 2 Pair 1 Inner Fan stopped due to rotor failure ----------> Major alarm set
These alarms are generated due to rotor failure on the fan tray. This leads to abnormal functionality of the fans and hence raising alarms.
The fan tray reporting this alarm needs to be replaced as it is hardware failure.
Please proceed with RMA of the fan tray.
Please open a case with JTAC Support for further investigation and assistance.
Initial Draft - 20/06/23
The fan tray operates as a single unit. If an individual fan in the tray fails, you must replace the entire fan tray. However, the fan tray continues to operate indefinitely and provides sufficient cooling even when a single fan rotor fails. The fan tray operates indefinitely provided that the room temperature is within the operating range.