Description

The FPC slot-0 and slot-11 on the MX960 router are not NEBS compliant beyond 104°F (40°C). This article explains that this is a cooling restriction.

This article affects only the following MPCs:

Symptoms

The operation of the FRU (installed onto FPC slot-0 and slot-11) is not guaranteed if the ambient temperature exceeds 104°F (40°C). If the ambient temperature continues to rise beyond 104°F (40°C), there could be overheating conditions at higher temperatures, exceeding chassis thresholds and resulting in shutdown conditions.

Solution

This is a cooling restriction.

The ambient temperature of 104°F (40°C) is measured at CB-slot 0 and 1 "Intake" and correlated to each FPC in an MX chassis.

user@lab-mx960-01> show chassis environment | match intake
<snip>
CB 0 Intake                    OK         27 degrees C / 80 degrees F
CB 1 Intake                    OK         27 degrees C / 80 degrees F
CB 2 Intake                    OK         27 degrees C / 80 degrees F
FPC 0 Intake                   OK         30 degrees C / 86 degrees F
FPC 1 Intake                   OK         29 degrees C / 84 degrees F
FPC 5 Intake                   OK         30 degrees C / 86 degrees F