The alarm indicates the corresponding zone in the chassis (in an MX2020 or MX2010) does not have sufficient power remaining to guarantee Power Supply Module (PSM) N+1 redundancy.
user@router> show chassis power -snip- System: Upper Zone: Capacity: 10500 W (maximum 10500 W) Allocated power: 4530 W (5970 W remaining) Actual usage: 805.19 W Lower Zone: Capacity: 8400 W (maximum 8400 W) Allocated power: 4530 W ( 3870 W remaining ) Actual usage: 828.00 W Total system capacity: 18900 W (maximum 18900 W) Total remaining power: 9840 W Notes: * 2100W x 5 PSM provides 10500W for upper zone. * 2100W x 4 PSM provides 8400W for lower zone. * Lower zone's remaining power is 3870W which is higher than PSM power rate 2100W.
user@router> show chassis power -snip- System: Upper Zone: Capacity: 10500 W (maximum 10500 W) Allocated power: 4530 W (5970 W remaining) Actual usage: 805.19 W Lower Zone: Capacity: 8400 W (maximum 8400 W) Allocated power: 4530 W ( 3870 W remaining ) Actual usage: 828.00 W Total system capacity: 18900 W (maximum 18900 W) Total remaining power: 9840 W
user@router> show chassis power -snip- System: Upper Zone: Capacity: 10500 W (maximum 10500 W) Allocated power: 4530 W (5970 W remaining) Actual usage: 948.06 W Lower Zone: Capacity: 6300 W (maximum 6300 W) Allocated power: 4530 W ( 1770 W remaining ) Actual usage: 1099.69 W Total system capacity: 16800 W (maximum 16800 W) Total remaining power: 7740 W
user@router> show chassis alarms 1 alarms currently active Alarm time Class Description 2013-11-20 22:39:18 PDT Minor N+1 Power redundancy missing in Lower zone
This informational log indicates that the chassis needs more power to guarantee PSM redundancy. Please calculate the power requirements using the related links below and add more PSM if it is needed.