This article explains how to address the following alarm:
2013-05-22 16:08:16 PDT Minor Mix of ENH-PEMs
The solution is to insert Power Entry Modules (PEMs) of the same type. This alarm does not impact service.
After swapping a PEM you may encounter the following alarm:
This is not a failure alarm and can easily be resolved.
The enhanced Power Entry Module (ENH-PEM) alarm is due to a mix of different PEM types.
For Example:
PEM 0 is PS 1.4-2.52kW; 90-264V AC in - MX480/MX240 2520W AC P/S, Base Bundle
PEM 1 is PS 1.2-1.7kW; 100-240V AC in - MX480 1200W AC P/S, Spare
This alarm can be cleared by inserting PEMs of the same type.
If that fails and the alarm continues, please contact JTAC to investigate the issue further.