Description

Per Input/source power numbers are not displayed on PTX10008 devices running with DC power input.

Whereas same routers with AC power supplies reports.


Please see the below output from a PTX10008 running 22.3X50.39-EVO. We have also confirmed this behavior on 22.3X50.66-J3.4-EVO.


show chassis power | no-more

Chassis Power Voltage(V) Power(W)


Total Input Power 8376

PSM 0

State: Online

Input A0 53 <<<<<<<<<<<<<<<<<<<<<<<<

Input B0 53

Input A1 53

Input B1 53

Output 12.33 1334.88 (60A input select)

PSM 1

State: Online

Input A0 53

Input B0 53

Input A1 53

Input B1 53

Output 12.33 1351.16 (60A input select)

PSM 2

State: Online

Input A0 53

Input B0 53

Input A1 53

Input B1 53

Output 12.33 1394.58 (60A input select)

PSM 3

State: Online

Input A0 53

Input B0 53

Input A1 53

Input B1 53

Output 12.35 1358.74 (60A input select)

PSM 4

State: Online

Input A0 53

Input B0 53

Input A1 53

Input B1 53

Output 12.49 1373.79 (60A input select)

PSM 5

State: Online

Input A0 53

Input B0 53

Input A1 53

Input B1 53

Output 12.33 1351.16 (60A input select)


System:

Zone 0:

Capacity: 26400 W (maximum 33000 W)

Allocated power: 18810 W (7590 W remaining)

Actual usage: 8376 W

Total system capacity: 26400 W (maximum 33000 W)

Total remaining power: 7590 W


{master}

```

Symptoms

Input Power values not reported when using the DC power sources.

Solution

This is expected behavior with the DC power sources, per source/Input power is not being reported.

Modification History

2025-10-06 : Article Created