SRX5800 Site Guidelines and Requirements:
Table 1 specifies the environmental specifications required for normal firewall operation. In addition, the site should be as dust-free as possible.
Description
Value
Altitude
No performance degradation to 10,000 ft (3048 m)
Relative humidity
Normal operation ensured in relative humidity range of 5% to 90%, noncondensing
Temperature
Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)
Nonoperating storage temperature in shipping crate: –40°F (–40°C) to 158°F (70°C)
Seismic
Tested to meet Telcordia Technologies Zone 4 earthquake requirements
Maximum thermal output
Standard-Capacity AC and DC power supplies
AC power: 20,160, BTU/hour (5912 W)
DC power: 17,057 BTU/hour (5002 W)
These specifications are estimates and subject to change.
High-Capacity AC and DC power supplies
AC power: 32,780 BTU/hour (9608 W)
DC power: 33,482 BTU/hour (9813 W)
NOTE: Install the firewall only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
Efficient device operation requires proper site planning. For the device to operate properly, you must ensure maintenance and proper layout of the equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally caused equipment failures:
Table 2 describes the factors you must consider while planning the electrical wiring at your site.
WARNING: You must provide a properly grounded and shielded environment and use electrical surge-suppression devices.
Site Wiring Factor
Guidelines
Signaling limitations
If your site experiences any of the following problems, consult experts in electrical surge suppression and shielding:
Radio frequency interference (RFI) because of improperly installed wires
Damage from lightning strikes occurring when wires exceed recommended distances or pass between buildings
Damage to unshielded conductors and electronic devices as a result of electromagnetic pulses (EMPs) caused by lightning
Radio frequency interference
To reduce or eliminate RFI from your site wiring, do the following:
Use a twisted-pair cable with a good distribution of grounding conductors.
If you need to exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal, when applicable.
Electromagnetic compatibility
If your site is susceptible to problems with electromagnetic compatibility (EMC), particularly from lightning or radio transmitters, seek expert advice.
Strong sources of electromagnetic interference (EMI) can cause:
Destruction of the signal drivers and receivers in the device.
Electrical hazards as a result of power surges conducted over the lines into the equipment.